返回
A new optimization design for grounding grid
DOI:10.1016/j.ijepes.2018.12.041.png)
摘要
En 中文
In this paper, a new approach for designing groudging grid is proposed. The design is based on contracting an auxiliary annular grounding grid and transforming the lingtning rod's grounding poing from main grounding grid to auxiliary grounding grid. Modal analysis and softwave simulataes is employed to obtain the transformed lightning current (and the voltage) and the reduced ressitance. The dual port model is used to calculate the impedance value of the grounding grid. The calculation results of the model are compared with the standard grounding body model EMF. At the same time, the relationship between the induced voltage of each point of the grounding grid and the distance of the lightning current injection point is studied by using the dual port model. The reduced resistance is simulated by building annular grounging grid model and square grounging grid model and making a comparison in performance betwen them. Farther, when there is a lingtning event, instead of providing a low impedance path by the main grounding grid, the design provide anther path by the auxilary grounding grid, which can transfer the lightning current into the auxilary grounding grid. All the model analysis and simulation results are presented and discussed in the paper.
Keyword:
Annular grounding grid
Counterattack
Lightning protection
Grounding resistance
Dual port
ATP-EMTP
AI总结
对已上传原文的论文进行重点信息的提取,主要内容包括:简要概述、研究摘要、背景介绍、关键亮点、图文解析、展望与总结。
期刊
I
IF:
5
论文数:
1.1W
被引数:
3.1W
机构
引用论文
Adjoint-state Reverse-time Migration for 4C Seismic Data - Application to Marine Seismic Imaging
Proceedings
IF0