返回
A validated three-node model for displacement ventilation
DOI:10.1016/j.buildenv.2014.10.029.png)
摘要
En 中文
Displacement ventilation (DV) systems are characterized by thermal stratification that cannot be adequately modeled using the fully mixed room air approach that is common in overhead air conditioning system design. This paper presents a simplified approach for DV that models the room thermal stratification using three air temperature nodes: lower layer (floor level), occupied zone and upper layer. The proposed approach is a development of one of the two models currently available in the thermal simulation tool EnergyPlus. A methodology for locating the neutral height in temperature profiles was developed. This methodology was used to verify the applicability of Morton et al. (1956) plume flow equation to predict the neutral level in DV rooms. The proposed model was successfully validated using nine different scenarios from three independent experimental studies. The model provides significantly improved precision when compared to existing DV nodal models, in particular in the floor level and occupied zone temperatures. (C) 2014 Elsevier Ltd. All rights reserved.
Keyword:
Displacement ventilation
Nodal model
Thermal plumes
Energy Plus
Neutral height
AI总结
对已上传原文的论文进行重点信息的提取,主要内容包括:简要概述、研究摘要、背景介绍、关键亮点、图文解析、展望与总结。
期刊
IF:
7.6
论文数:
1.3W
被引数:
6.6W
机构
引用论文
Development of new and validation of existing convection correlations for rooms with displacement ventilation systems
ENERGY AND BUILDINGS
IF7.1
Modelling the effect of an occupant on displacement ventilation with computational fluid dynamics
ENERGY AND BUILDINGS
IF7.1