返回
Backup Protection Algorithm for Failures in Modular DC Circuit Breakers
DOI:10.1109/TPWRD.2020.3045262.png)
摘要
En 中文
HVDC grid protection with adequate speed and reliability is required to minimise the impact of DC faults. In particular, fast breaker failure backup protection algorithms are needed to meet the expected reliability requirements of HVDC grids. In this paper, existing breaker failure backup protection algorithms are shown inadequate to detect partial failures like a single module failure of breakers with a modular structure. This paper proposes a backup protection algorithm which rapidly detects a DC breaker failure based on estimating the counter-voltage created by the energy absorption branch during an interruption. The performance of the proposed algorithm is evaluated using a four-terminal test network with both hybrid and mechanical DC breaker technologies. The simulation results show that the proposed algorithm is able to quickly detect both complete and partial failures of the two breaker technologies even considering measurement errors, noise and ageing of the energy absorption components.
Keyword:
HVDC transmission
Circuit faults
Absorption
Surges
Arresters
Power system reliability
Circuit breakers
HVDC grid protection
DC circuit breaker
breaker failure
backup protection algorithm