Complex Dissipating Energy Flow Method for Forced Oscillation Source Location
DOI:10.1109/TPWRS.2022.3184119.png)
摘要
En 中文
In this letter we propose an extension of the Dissipating Energy Flow (DEF) method for locating sources of forced oscillations (FOs), based on an energy function constructed by the complex integral approach, which we call Complex DEF (CDEF). To trace sources of FO, we study the scalar projection of CDEF in a specific direction on the complex plane. We show by simulated cases that this alternative has a good performance in cases where the original DEF fails.
Keyword:
Generators
Voltage
Oscillators
Damping
Position measurement
Transient analysis
Phasor measurement units
Dissipating energy flow
energy functions
forced oscillations source location
phasor measurement unit (PMU)