返回
DSTATCOM allocation in distribution networks considering load variations using bat algorithm
DOI:10.1016/j.asej.2015.08.006.png)
摘要
En 中文
This paper proposes a new method of scheduling for optimal placement and sizing of Distribution STATic COMpensator in the radial distribution networks to minimize the power loss. In the proposed method Voltage Stability Index is used to search the optimal placement for installation of DSTATCOM. Optimal size of DSTATCOM is found by using bat algorithm. The feeder loads are varied by linearly from light load to peak load with a step size of 1%. In each load step, the optimal placement and sizing for DSTATCOM are calculated. By using the Curve Fitting Technique, the optimal sizing for DSTATCOM per load level is formulated in the form of generalized equation. The proposed approach will help the Distribution Network Operators to select the DSTATCOM size according to the load changes. To check the feasibility of the proposed method, system has been tested on two standard buses such as IEEE 33 and 69 bus radial distribution systems. (C) 2015 Ain Shams University. Production and hosting by Elsevier B.V.
Keyword:
Distribution STATic COMpensator (DSTATCOM)
Bat algorithm
Voltage Stability Index (VSI)
Distribution Network Operators (DNOs)
Curve Fitting Technique (CFT)
AI总结
对已上传原文的论文进行重点信息的提取,主要内容包括:简要概述、研究摘要、背景介绍、关键亮点、图文解析、展望与总结。
期刊
IF:
5.9
论文数:
3.4K
被引数:
1.2W
机构
暂无机构信息
引用论文
Optimal location and sizing of capacitor placement in radial distribution system using Bacterial Foraging Optimization Algorithm使用细菌觅食优化算法在径向配电系统中优化电容器的位置和尺寸