Evaluating harmonic-induced transformer heating

delete1996-01-01
delete33
PRE
AI
M
M.T. Bishop *
B
Baranowski, JF
D
D. Heath
S
S.J. Benna
DOI:10.1109/61.484029delete
delete原文链接
delete原文求助
delete分享
delete收藏
摘要

摘要

En 中文
The proliferation of non-linear loads on power systems has increased the awareness of the potential reduction of a transformer's life due to increased losses. Over the past few years, several manufacturers and users have been applying a harmonic rating system to specify transformers based on relationships developed in ANSI/IEEE C57.110 [1]. The specification or evaluation of transformers in a harmonic environment requires a knowledge of the load mix as well as details of the load current harmonic content. The additional heating experienced by a transformer depends on the harmonic content of the load current, and the design of the unit. A heat run circuit was devised to produce harmonic rich load current on a 25 kVA oil-immersed distribution transformer. The test was conducted at 100% of nameplate current using a purely resistive load, and a 2.4 ms current pulse. The temperature rise experienced under harmonic excitation was observed and documented [2].