返回
Evaluating harmonic-induced transformer heating
DOI:10.1109/61.484029.png)
摘要
En 中文
The proliferation of non-linear loads on power systems has increased the awareness of the potential reduction of a transformer's life due to increased losses. Over the past few years, several manufacturers and users have been applying a harmonic rating system to specify transformers based on relationships developed in ANSI/IEEE C57.110 [1]. The specification or evaluation of transformers in a harmonic environment requires a knowledge of the load mix as well as details of the load current harmonic content. The additional heating experienced by a transformer depends on the harmonic content of the load current, and the design of the unit. A heat run circuit was devised to produce harmonic rich load current on a 25 kVA oil-immersed distribution transformer. The test was conducted at 100% of nameplate current using a purely resistive load, and a 2.4 ms current pulse. The temperature rise experienced under harmonic excitation was observed and documented [2].
Keyword:
harmonics
transformer heating
transformer losses
AI总结
对已上传原文的论文进行重点信息的提取,主要内容包括:简要概述、研究摘要、背景介绍、关键亮点、图文解析、展望与总结。

