返回
Indirect-Direct Secure Load Frequency Control Against False Data Injection Attacks
DOI:10.1109/TII.2023.3330235.png)
摘要
En 中文
An indirect-direct secure control (IDSC) method is proposed for load frequency control (LFC) of multi-area power system under false data injection attacks. In the indirect secure control, based on the inherent local security of primary frequency control, an estimation system in power plant is established to reconstruct LFC commands. In the direct secure control, PI-based LFC scheme is adopted with a new robust performance index. Thus, a complementary secure strategy realized by IDSC is developed from combining resilience to cyber-physical disturbances and elimination of attack intrusion. We adopt mixed $H_{\infty }/H_{2}$ control method to formulate and design interconnected IDSC and decentralized IDSC. Simulations of the three-area power systems are carried out to verify the validness of our proposed IDSC method.
Keyword:
Resilience
Frequency control
Security
Observers
Linear feedback control systems
Informatics
Estimation error
False data injection (FDI) attack
indirect-direct secure control (IDSC)
load frequency control (LFC)
mixed H-infinity/H-2 control
期刊
IF:
9.9
论文数:
8.6K
被引数:
6.0W
机构
引用论文
Stability Assessment of Secondary Frequency Control System With Dynamic False Data Injection Attacks
Secure Event-Triggered Sliding Control for Path Following of Autonomous Vehicles Under Sensor and Actuator Attacks传感器和执行器攻击下自动驾驶汽车路径跟踪的安全事件触发滑动控制