返回
Line Outage Detection Using Phasor Angle Measurements
DOI:10.1109/TPWRS.2008.2004826.png)
摘要
En 中文
Although phasor measurement units (PMUs) have become increasingly widespread throughout power networks, the buses monitored by PMUs still constitute a very small percentage of the total number of system buses. Our research explores methods to derive useful information from PMU data in spite of this limited coverage. In particular, we have developed an algorithm which uses known system topology information, together with PMU phasor angle measurements, to detect system line outages. In addition to determining the outaged line, the algorithm also provides an estimate of the pre-outage flow on the outaged line. To demonstrate the effectiveness of our approach, the algorithm is demonstrated using simulated and real PMU data from two systems-a 37-bus study case and the TVA control area.
Keyword:
Event detection
line outages
phasor measurement units
AI总结
对已上传原文的论文进行重点信息的提取,主要内容包括:简要概述、研究摘要、背景介绍、关键亮点、图文解析、展望与总结。
期刊
IF:
7.2
论文数:
1.1W
被引数:
5.0W
机构
引用论文
1,1-Ethylene-1H-azulenium ion and its alkyl substituted derivatives: Synthesis, characterization, and some reactions thereof
Tetrahedron
IF0