返回
Multiple-frequency three-phase load flow for harmonic analysis
DOI:10.1109/TPWRS.2004.825906.png)
摘要
En 中文
A multiple-frequency three-phase load-flow model was developed in this paper. There are two new submodels including the fundamental power flow (FPF) and harmonic frequency power-flow (HPF) model. In FPF, models of electrical elements and PV buses were treated in the form of current injections in a transmission system. The standard Fourier analysis was used to deal with the harmonic loads to get injection currents. With harmonic currents as equivalent current sources, the HPF can be derived. Besides, the decoupled fast version of FPF and HPF, called DFPF and DHPF, were also proposed in this paper. Test results show that the proposed general-purpose methods are better performers than conventional power-flow solutions and are very robust.
Keyword:
decoupled model
equivalent-current-injection (ECI)
fundamental power flow (FPF)
harmonic power flow (HPF)
PV bus
AI总结
对已上传原文的论文进行重点信息的提取,主要内容包括:简要概述、研究摘要、背景介绍、关键亮点、图文解析、展望与总结。
期刊
IF:
7.2
论文数:
1.1W
被引数:
5.0W
机构
暂无机构信息
引用论文
Three-phase unbalanced distribution power flow solutions with minimum data preparation具有最小数据准备的三相不平衡配电潮流解决方案