返回
Observability-Aware Resilient PMU Networking
DOI:10.1109/TPWRS.2024.3387338.png)
摘要
En 中文
The essential role of the phasor measurement unit (PMU) network is to keep power grid observable to system operators in normal and component failure conditions. In this article, an observability-aware PMU networking framework is proposed for enabling fast and resilient data transfer from the PMUs to phasor data concentrators (PDCs) to support real-time power grid monitoring needs. The proposed algorithm analyzes the interdependent roles of PMUs in observing buses determined by the power grid topology and integrate them into a resilient data routing scheme over the communication network topology. By exploiting the multi-domain information, the proposed routing framework minimizes the end-to-end delay in the network while keeping the observability of power grid resilient against user-defined PMU and communication failure scenarios. Simulation results validate the proposed algorithm's superiority over general resilient routing algorithms that are agnostic to the domain knowledge of power grid observability.
Keyword:
Phasor measurement units
Power grids
Observability
Routing
Delays
Topology
Network topology
Latency
observability
PMU
power system communication
power system monitoring
resilience
routing
situational awareness
WAMS
期刊
IF:
7.2
论文数:
1.1W
被引数:
5.0W
机构
引用论文
Software Defined Networks-Based Smart Grid Communication: A Comprehensive Survey基于软件定义网络的智能电网通信: 综合综述
Synchrophasor Measurement Technology in Power Systems: Panorama and State-of-the-Art
IEEE ACCESS
IF3.6