返回
Optimal Phase Balancing in Electricity Distribution Feeders Using Mixed-Integer Linear Programming
DOI:10.3390/su15054473.png)
摘要
En 中文
A mixed-integer linear programming (MILP) model that includes reductions in neutral current, feeder energy-loss cost, customer interruption cost, and labor cost is developed to derive the optimal phase-swapping strategy to enhance the phase balancing of distribution feeders. The neutral current of the distribution feeder is reduced by the phase-swapping strategy so that the tripping of the low-energy overcurrent relay can be prevented and customer-service interruption costs and the labor cost to execute the phase-swapping works can be justified by the energy-loss reduction obtained. The novelty of the study is its derivation of the phase-swapping strategy using mixed-integer linear programming to solve the problem of the unbalance of the distribution feeders. A Taipower distribution feeder is used to derive the phase-swapping strategy to demonstrate the proposed MILP model for phase balancing. The comparison of the phase currents and neutral current before phase-swapping reveals that the three-phase balance was not only significantly improved, but that the voltage unbalance was also decreased dramatically using the proposed phase-swapping strategy.
Keyword:
mixed-integer linear programming
outage management system
phasing unbalance index
voltage unbalance factor
期刊
IF:
3.3
论文数:
10.7W
被引数:
28.4W
机构
引用论文
Multi-Source Data-Cooperated Neutral Low-Resistance Grounding Cable Grid Faulty Segment Identification多源数据协同中性点低电阻接地电缆电网故障段识别