arrow
返回

Optimizing generator reactive power resources

delete1999-01-01
delete12
PRE
AI
A
Adibi, MM *
M
Milanicz, DP
V
Volkmann, TL
DOI:10.1109/59.744550delete
delete原文链接
delete原文求助
delete分享
delete收藏
摘要

摘要

En 中文
A method is described for selecting generator step-up and auxiliary transformer tap positions to provide the desired reactive power requirements in a coal burning power plant. It is shown how a generator could be made to absorb reactive power, when previously unable to do so, by adjustment of tap positions on the generator step-up and auxiliary transformers. The approach described provides an indication of the range of reactive power outputs that are available for different tap positions. This information would facilitate the alteration of transformer tap positions to make more effective use of generator reactive power resources.