Performance evaluation and parametric studies on variable nozzle ejector using R134A
DOI:10.1016/j.csite.2018.04.006.png)
摘要
En 中文
Computational fluid dynamics of variable nozzle ejector has been studied to determine the optimum nozzle exit position for reliable ejector cooling cycle operations. The flow rates of primary and secondary stream were varied to obtain the optimum entrainment ratio under different ranges of operating conditions. The refrigerant R134a was chosen based on the merit of its environmental and performance characteristics, the refrigerant was chosen because currently is used widely in air conditioning system. It was found that the computational fluid dynamics showed that the optimum positioning of nozzle exit position, which was based on the parameters such as pressure inlet variation the temperature inlet. The results obtained after the optimization of the results showed that the optimum nozzle exit position was found at 3 mm from the mixing chamber inlet when the operating conditions pressure inlet, secondary pressure inlet, primary temperature inlet and outlet pressure were at (18bar, 6bar, 373K, and5.6bar) respectively. Similarly, the range of entrainment ratio was varied between 0.24 - 1.283 at a constant area ratio, and at varied operating conditions.
Keyword:
Ejector
Variable nozzle
Cooling system
Entrainment ratio
Turbulence models
AI总结
对已上传原文的论文进行重点信息的提取,主要内容包括:简要概述、研究摘要、背景介绍、关键亮点、图文解析、展望与总结。
期刊
IF:
6.4
论文数:
8.1K
被引数:
2.6W
机构
引用论文
Reducing energy consumption of a steam ejector through experimental optimization of the nozzle geometry
ENERGY
IF9.4
Pressure recovery ratio in a variable cooling loads ejector-based multi-evaporator refrigeration system基于可变冷却负荷喷射器的多蒸发器制冷系统中的压力恢复率
ENERGY
IF9.4
The behaviour of a hybrid compressor and ejector refrigeration system with refrigerants 134a and 142b具有制冷剂134a和142b的混合压缩机和喷射器制冷系统的行为