Smart Grid Data Integrity Attacks
DOI:10.1109/TSG.2013.2245155.png)
摘要
En 中文
Real power injections at loads and generators, and real power flows on selected lines in a transmission network are monitored and transmitted over a SCADA network to the system operator. These are used in state estimation algorithms to make dispatch, re-balance and other energy management system [EMS] decisions. Coordinated cyber attacks on power meter readings can be designed to be undetectable by any bad data detection algorithm. These unobservable attacks present a serious threat to grid operations. Of particular interest are sparse attacks that involve the compromise of a modest number of meter readings. An efficient algorithm to find all unobservable attacks [under standard DC load flow approximations] involving the compromise of exactly two power injection meters and an arbitrary number of power meters on lines is presented. This requires O(n(2)m) flops for a power system with buses and line meters. If all lines are metered, there exist canonical forms that characterize all 3, 4, and 5-sparse unobservable attacks. These can be quickly detected with O(n(2)) flops using standard graph algorithms. Known-secure phasor measurement units [PMUs] can be used as countermeasures against a given collection of cyber attacks. Finding the minimum number of necessary PMUs is NP-hard. It is shown that p + 1 PMUs at carefully chosen buses are sufficient to neutralize a collection of cyber attacks.
Keyword:
Cybersecurity
integrity attacks
observability
smart grid
synchro-phasors