arrow
Return

Accurate Measurement of Tower Grounding Resistance for Single-Tower and Multi-Tower Parallel Scenarios Based on the Clamp Meter Method: For the Sustainable Operation of Towers

delete2024-08-31
delete0
delete
OA
AI
Y
Y. H. Zhang
Z
Zoujun Wang
K
Kaiwen Feng
Y
Yirui Zhang
Z
Zhitong Tian
Z
Zhihui Zheng
H
Hailiang Lu *
DOI:10.3390/su16177551delete
deleteOriginal
deleteOriginal request for help
deleteShare
deleteSave
Abstract

Abstract

En 中文
Transmission tower grounding safety is a critical element that significantly impacts the reliability and sustainability of power grids. Tower grounding resistance is a significant grounding characteristic parameter. In order to accurately measure the grounding resistance of towers using the clamp meter method in both single-tower and multi-tower parallel scenarios, this paper establishes theoretical calculation models for measuring tower grounding resistance using the clamp meter method. Considering the interaction between the artificial grounding device and the tower foundation, this paper models and simulates transmission towers and lightning shield wires, analyzing the influencing factors on the grounding resistance measurement results using the clamp meter method in both single- and multi-tower parallel scenarios. The results show that for single towers, the clamp meter measurement results increase with decreasing foundation root spacing and increasing length of the artificial device's extension lines, but the changes are relatively small. In multi-tower grounding scenarios, due to the shunting effect of the parallel branches formed by the towers and lightning shield wires, the value is smaller than in single-tower grounding scenarios. Changing the number of parallel towers and the type of lightning shield wire produces little effect on the measurement results. However, changes in soil resistivity have the most significant impact. Therefore, correction formulas for the impact of soil resistivity on clamp meter measurements are proposed and then verified by applying them to field tests.
Keywords:
grounding characteristic parameter
clamp meter method
tower foundation grounding device
artificial grounding device
current shunt of towers

Journal

Sustainability cover
Sustainability
IF:
3.3
Papers:
10.5W
Citations:
28.4W

Organization

W
wuhan university
Scholars:
7.9W
Papers: 5.7W
Citations: 70