Return
Chiller-pump system optimisation method for minimum energy operation based on multi-objective evolutionary algorithm
DOI:10.1016/j.applthermaleng.2022.118150.png)
Abstract
En 中文
The operation optimisation of chilled water systems, comprising chillers and pumps, should consider variations in the cooling demand. Although a number of approaches have been proposed, achieving an overall optimum in actual operation is complicated. Herein, we propose a hybrid optimisation method for a chiller-pump system in parallel-arranged systems with non-identical chillers and pumps, which are commonly applied in engineering practice but are rarely considered in the literature. A holistic optimisation based on a multi-objective evolutionary algorithm was conducted for the overall minimum energy by solving the trade-off problem between chillers and pumps. The overall energy consumption and system flow violation were simultaneously minimised by optimising practical parameters, including binary (alpha(chiller,i), alpha(pump,j)) and continuous ((Q) over dot(chiller,i), omega(j), (m) over dot(chw,j)) variables. The proposed method was evaluated via a simulation. The results suggest that the optimisation is rational, and energy saving ratios of 7.3%, 5.3%, and 34.0% for overall, chillers, and pumps, respectively, can be achieved relative to the baseline.
Keywords:
HVAC
Chiller -pump system
Optimisation
Multi-objective evolutionary algorithm
Energy saving
Journal
IF:
6.9
Papers:
2.8W
Citations:
14.0W
Organization
Cited Papers
Supervisory and optimal control of central chiller plants using simplified adaptive models and genetic algorithm
APPLIED ENERGY
IF11
Optimal chiller loading by genetic algorithm for reducing energy consumption
ENERGY AND BUILDINGS
IF7.1