Developing a simplified model for evaluating chiller-system configurations
DOI:10.1016/j.apenergy.2006.07.006.png)
Abstract
En 中文
Optimizing system configuration is always an interest of building designers. By statistical analysis of the design data of 50 commercial buildings in Hong Kong and the performance data of 186 chiller models, it is ascertained that the chiller capacity and the fraction of full-load capacity have little influence on the system's energy performance. Following on this, this paper presents an evaluation of the energy performance of a multiple-chiller system consisting of 2-10 equally sized chillers. Such an analysis was based on performance data from three major manufacturers. It is found that the energy efficiency of multiple-chiller system improves with a higher number of chillers, and the maximum saving is estimated to be 9.5%. Based on the results of the study, a simplified model relating energy use with number of chillers has been established. The model can help designers more quickly determine how the energy efficiency can be weighted against other factors, such as the additional plant room space and the financial implications. (c) 2006 Elsevier Ltd. All rights reserved.
Keywords:
multiple chiller
system configurations
part-load performance
statistical analysis
AI Summary
Key information extracted from the uploaded paper, including a brief overview, abstract, background, key highlights, visual analysis, and future outlook.
Journal
IF:
11
Papers:
2.6W
Citations:
17.8W
Organization
No organization information available
Cited Papers
Applying condensing-temperature control in air-cooled reciprocating water chillers for energy efficiency
APPLIED ENERGY
IF11
Optimal chiller loading by genetic algorithm for reducing energy consumption
ENERGY AND BUILDINGS
IF7.1
Thermodynamic-behaviour model for air-cooled screw chillers with a variable set-point condensing temperature
APPLIED ENERGY
IF11