Return
Effect of reduced evaporator airflow on the high temperature performance of air conditioners
R
D
M
S
DOI:10.1016/S0378-7788(96)00976-0.png)
Abstract
En 中文
Two residential sized air conditioners were tested in psychrometric rooms at reduced evaporator airflows ranging from Oto 50% below that recommended by the manufacture of each of the units. Outdoor temperatures ranged from 35 to 49 degrees C, One of the units used a thermal expansion valve for flow control while the other unit used a short tube orifice. Performance of the units was quantified by the capacity, power, coefficient of performance, and sensible heat ratio. Results at 35 degrees C indicated that the reduction in air produced a larger drop in capacity and coefficient of performance for the orifice controlled unit than the thermal expansion valve controlled unit. The power showed less than a 4% reduction for either unit as the airflow was reduced by 50%.
Keywords:
evaporator airflow
high temperature performance
air conditioners
AI Summary
Key information extracted from the uploaded paper, including a brief overview, abstract, background, key highlights, visual analysis, and future outlook.
Journal
IF:
7.1
Papers:
1.5W
Citations:
6.8W
Organization
No organization information available
