Return
Energy and thermo-hydraulic analysis of multi-configuration borehole heat exchanger fields: Insights from a large-scale geothermal plant
A
M
R
DOI:10.1016/j.ecmx.2026.102151.png)
Abstract
En 中文
• Full-year operational data from a 120-borehole, 2.6 MW GSHP–BHE system is analyzed. • Geometry-normalized loading separates field-scale capacity from local borehole stress. • Winter borehole-scale loading converges across HX types at − 17.5 to − 19.0 W/m. • Local thermo-hydraulic efficiency follows E-Turbo > Double-U > Single-U based on ΔT reduction. • Summer recharge compensates only 25.5–28.4% of extraction, confirming annual imbalance.
Keywords:
Shallow geothermal energy
Borehole heat exchanger (BHE)
Thermo-hydraulic behaviour
Real operational data
Ground heat transfer
AI Summary
Key information extracted from the uploaded paper, including a brief overview, abstract, background, key highlights, visual analysis, and future outlook.
Journal
E
IF:
7.6
Papers:
1.1K
Citations:
4.5K
Organization