1
Return

Geomagnetically Induced Currents, Transformer Harmonics, and Reactive Power Impacts: Observed Response of a Single-Phase Transformer in New Zealand

delete2026-06-09
delete0
delete
OA
AI
X
Xinhu Feng
C
Craig J. Rodger
M
Mark A. Clilverd *
D
Daniel H. Mac Manus
V
Victor Lo
M
Michael D Dalzell
A
A. Renton
A
Andrew Lapthorn
J
J. B. Brundell
T
Tanja Petersen
DOI:10.1029/2026SW004966delete
deleteOriginal
deleteShare
deleteSave
View PDF
Abstract

Abstract

En 中文
Geomagnetic storms represent a space weather hazard to power transmission networks due to the effects of induced geo-electric fields within the conducting surface of the Earth. These drive electric currents in power transmission lines which can flow to ground through the neutral-ground connections of transformers. Geomagnetically induced currents (GIC) can negatively impact the operation of high voltage transformers through asymmetric half-cycle transformer core saturation. In this study GIC measurements, derived effective current, and reactive power responses (Q) of the single-phase bank autotransformer, T4, operating at 220 kV in the Halfway Bush substation, Dunedin, New Zealand have been analyzed over the period 2013–2017. During 8 elevated GIC events linear enhancements of reactive power consumption (Qcon, MVAr) occurred, even with comparatively low levels of GIC (i.e., <7 A). This is consistent with transformer core saturation where there is little tolerance or “headroom” to GIC in the design for single-phase bank transformers. Reactive power measurements show high variability. The removal of the non-GIC variability is difficult and introduces uncertainty into the identification of GIC-driven responses. In this analysis we consider two techniques to isolate GIC-induced reactive power responses. We find that transformer T4 exhibited a reactive power response of ∼0.115 MVAr/A. The results are a factor of 2–3 larger than MVAr changes in a nearby three-phase, three-limb autotransformer, aligning with previous research. The results are consistent with, but less extreme than modeling studies found for transformer units operating at significantly higher voltages.
Keywords:
space weather
GIC
autotransformer
reactive power
transpower
geomagnetic storms
AI Summary

AI Summary

Key information extracted from the uploaded paper, including a brief overview, abstract, background, key highlights, visual analysis, and future outlook.

Journal

S
space weather
IF:
0
Papers:
115
Citations:
0

Organization

T
transpower new zealand limited
Scholars:
6
Papers: 3
Citations: 0
B
British Antarctic Survey
Scholars:
141
Papers: 84
Citations: 2.5K
U
university of canterbury
Scholars:
1.1K
Papers: 536
Citations: 0
E
earth sciences new zealand
Scholars:
328
Papers: 151
Citations: 0
U
university of otago
Scholars:
1.7W
Papers: 1.6W
Citations: 15
Cited Papers

Cited Papers

Citing Papers

Citing Papers