arrow
Return

Identifying Harmonic Attributes From Online Partial Discharge Data

delete2011-07-01
delete18
delete
OA
AI
V
Victoria M. Catterson *
S
S. Bahadoorsingh
S
S. E. Rudd
S
S.D.J. McArthur
S
Simon Rowland
DOI:10.1109/TPWRD.2011.2114373delete
deleteOriginal
deleteShare
deleteSave
View PDF
Abstract

Abstract

En 中文
Partial discharge (PD) monitoring is a key method of tracking fault progression and degradation of insulation systems. Recent research discovered that the harmonic regime experienced by the plant also affects the PD pattern, questioning the conclusions about equipment health drawn from PD data. This paper presents the design and creation of an online system for harmonic circumstance monitoring of distribution cables, using only PD data. Based on machine learning techniques, the system can assess the prevalence of the 5th and 7th harmonic orders over the monitoring period. This information is key for asset managers to draw correct conclusions about the remaining life of polymeric cable insulation, and prevent overestimation of the degradation trend.
Keywords:
Dielectric breakdown
epoxy resin insulation
monitoring
partial discharge (PD)
power quality (PQ)
power system harmonics
AI Summary

AI Summary

Key information extracted from the uploaded paper, including a brief overview, abstract, background, key highlights, visual analysis, and future outlook.

Journal

IEEE Transactions on Power Delivery cover
IEEE Transactions on Power Delivery
IF:
3.7
Papers:
9.1K
Citations:
2.2W

Organization

U
university west indies saint augustine
Scholars:
949
Papers: 731
Citations: 0
U
university west indies mona jamaica
Scholars:
3.4K
Papers: 2.5K
Citations: 1
U
university of strathclyde
Scholars:
1.1W
Papers: 1.1W
Citations: 12
researcher View more organizations