New Method for Synchronous Generator Parameters Estimation Using Load Rejection Tests Data Considering Operational Limitations

delete2021-03-01
delete19
PRE
AI
A
Alireza Arastou *
M
M. Karrari
B
Behrooz Zaker
DOI:10.1016/j.epsr.2020.106999delete
deleteOriginal
deleteOriginal request for help
deleteShare
deleteSave
Abstract

Abstract

En 中文
Load rejection (LR) test, recommended by different standards including IEEE Std.115., is considered as one of the most popular methods for parameter estimation of the synchronous generator (SG). However, parameter identification using this method has demonstrated no acceptable results for experimental data. Therefore, the present study aims to analyze common LR test operational limitations and to suggest a new method for parameter estimation based on LR test results which overcome the shortcomings of the previous method. To this end, a new approach is proposed for SG parameter estimation using LR test data. Using the proposed method, parameter estimation covers both salient pole and round rotor SGs. In both d and q axes, the effects of limitations are considered, and finally, parameters are estimated by fitting curve to experimental data based on the non-linear least square method and the genetic algorithm (GA). The proposed method is applied to the 200 MVA gas unit of a combined cycle power plant, and the results are discussed accordingly.
Keywords:
Synchronous generator
Load rejection test
Magnetic saturation
Parameter estimation
Non-linear least squares
Genetic Algorithm
AI Summary

AI Summary

Key information extracted from the uploaded paper, including a brief overview, abstract, background, key highlights, visual analysis, and future outlook.

Journal

Electric Power Systems Research cover
Electric Power Systems Research
IF:
4.2
Papers:
1.1W
Citations:
2.2W

Organization

A
Amirkabir University of Technology
Scholars:
1.1W
Papers: 1.1W
Citations: 1.0W
S
Shiraz University
Scholars:
8.1K
Papers: 7.5K
Citations: 7.4K