arrow
Return

Spray absorbers in absorption systems using lithium nitrate-ammonia solution

delete2005-06-01
delete38
PRE
AI
M
M. Venegas
P
Pedro Rodríguez
A
A. Lecuona
M
M. Izquierdo
DOI:10.1016/j.ijrefrig.2004.10.005delete
deleteOriginal
deleteOriginal request for help
deleteShare
deleteSave
Abstract

Abstract

En 中文
In the present work, the spray absorption method is studied for the absorption of ammonia refrigerant vapour by lithium nitrate-ammonia solutions. Mass transfer coefficients attainable using the spray absorption method are estimated. In this study the low-pressure absorber of a double-stage absorption refrigeration system is considered. Results show that the mass transferred is maximum (about 60% of the total) during the deceleration period of the drops. This period represents about 13.4% of the time required to reach the equilibrium state at the end of the absorption chamber. The results show that a time-average mass transfer coefficient equal to k(m) = 18.6 X 10(-5) m s(-1) may be attained. (c) 2004 Elsevier Ltd and IIR. All rights reserved.
Keywords:
absorption system
ammonia
solution
nitrate
process
spray
calculation
mass transfer

Journal

International Journal of Refrigeration cover
International Journal of Refrigeration
IF:
3.8
Papers:
2.7K
Citations:
1.8W

Organization

No organization information available