返回
A novel islanding detection method for microgrids based on variable impedance insertion
DOI:10.1016/j.epsr.2014.12.004.png)
摘要
En 中文
Islanding is the situation in which part of the power grid, consisting of load and distributed generation (DG) is isolated from the utility grid remaining active, i.e. serving load. The idea of islanding parts of the distribution network in case of faults, in order to increase the consumer quality of service, is the basic notion behind the formation of Microgrids. In the context of Microgrids, it becomes necessary to distinguish between intended islanding e.g. due to maintenance and unintended islanding due to faults at the upstream grid. When the emergency situation ceases, the Microgrid should reconnect seamlessly to the upper grid. In this paper, an islanding detection method (IDM) is proposed that is based on the insertion of a suitable, variable impedance at the low voltage side of the Grid. Islanding detection is effected by an intelligent agent embedded into the Microgrid's Central switch, which is transformed to a hybrid automatic transfer switch (HATS). The HATS agent detects the operation mode of the Microgrid based on local measurements and supervises the grid status. Both simulation studies and hardware laboratory tests are presented showing the performance and feasibility of the proposed method. (C) 2014 Elsevier B.V. All rights reserved.
Keyword:
Islanding detection method
Microgrids
Smart grids
Agents
Non detection zone (NDZ)
AI总结
对已上传原文的论文进行重点信息的提取,主要内容包括:简要概述、研究摘要、背景介绍、关键亮点、图文解析、展望与总结。
期刊
IF:
4.2
论文数:
1.2W
被引数:
2.2W
机构
引用论文
没有更多内容