Optimal transformer tap selection using modified barrier-augmented Lagrangian method
DOI:10.1109/TPWRS.2002.807093.png)
摘要
En 中文
The optimal tap selection of transformers directly connected to generators is one of the two significant industry problems. The generator stepup and auxiliary transformers generally are equipped with no-load (fixed) taps that are infrequently changed. Their optimum positions need to be determined for meeting power system discrete states over long periods, covering the annual light-load, peak-load, and emergency conditions. The other and related problem is the use of design reactive capability of generators rather than their actual operating limits. This paper reports on application of a modified barrier-augmented Lagrangian (MBAL)-based nonlinear optimal power-flow method for the optimum selections of the transformer tap positions and the voltage set points of the generators within their over and underexcitation operating limits. The feasibility of the method is demonstrated using a 160-bus test system in operation at a midatlantic utility. It is shown that the method minimizes the deviations of the system bus voltages from the unity while meeting the power system equality and inequality constraints under lightand peak-load conditions.
Keyword:
generator reactive capability
generator tap selection
optimal power flow
AI总结
对已上传原文的论文进行重点信息的提取,主要内容包括:简要概述、研究摘要、背景介绍、关键亮点、图文解析、展望与总结。
期刊
IF:
7.2
论文数:
1.1W
被引数:
5.0W
机构
暂无机构信息
引用论文
An efficient interior point method for sequential quadratic programming based optimal power flow基于序列二次规划的最优潮流的有效内点方法